C.10 enter command, Enter command types – Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 229

Advertising
background image

C.10 Enter Command

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

229

MEMO

BUS/Mod

bus

Co

mmunica

tion

s

C

C.10 Enter Command

When writing parameters to the converter from the PLC using MEMOBUS/Modbus communication, parameter H5-11
determines whether an Enter command must be issued to enable these parameters. This section describes the types and
functions of the Enter commands.

Enter Command Types

The converter supports two types of Enter commands as shown in

Table C.7

. An Enter command is enabled by writing 0

to register numbers 0900H or 0910H. It is only possible to write to these registers; attempting to read from these registers
will cause an error.

Table C.7 Enter Command Types

Note: The EEPROM can only be written to 100,000 times, so it is recommended to limit the number of times writing to the EEPROM.

The Enter command registers are write-only and if these registers are read, the register address will be invalid (Error code: 02H).
An Enter command is not required when reference or broadcast data are sent to the converter.

Register No.

Description

0900H

Simultaneously writes data into the EEPROM (non-volatile memory) of the converter and enables the data in RAM.
Parameter changes remain after cycling power.

0910H

Writes data in the RAM only. Parameter changes are lost when the converter is shut off.