3.2 Standard Connection Diagram

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

49

El

ec

tr

ical

I

n

st

al

lat

ion

3

Figure 3.1

Figure 3.1 Standard Connection Diagram (example: model 2A0030 to 2A0130, and 4A0030 to 4A0185)

<1> Do not use a line longer than 10 m (32.8 ft) to connect the input-side AC reactor and the converter.

<2> Use the specified AC reactor and harmonic filter module. Non-specified devices may cause erroneous operation.

<3> Do not use a DC bus line that is longer than 5 m (16.4 ft) to connect the converter and drive.

<4> Sequence the operation so that the converter starts operation before the drive when power is applied. Sequence the stopping

operation to turn off the drive first, then the motor, and finally the converter. Operating the drive without operating the converter or

turning off the power supply unit during operation may trigger a converter fault.

<5> Do not connect a power supply to the drive AC power supply terminals (R/L1, S/L2, and T/L3).

<6> The connections are shown for sequence connections with no-voltage contacts or NPN transistors for the sequence input signals

(S1 to S8). Use jumper S3 to select between Sink mode and Source mode. The default setting is Sink mode.

<7> Multi-function analog outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are

not intended for use as a feedback-type signal.

M

D1000

+

-

r1/ 11

1/ 21

t1/ 31

S1

S2

S3

S4

S5

S6

S7

S8

E(G)

RUN-SB

External fault

Fault reset

(Reserved)

(Reserved)

(Reserved)

External
Baseblock

Shield ground terminal

STOP

V

I

MEMOBUS/
Modbus Communication
RS-422/RS-485
max. 115.2 kbps

+

1

-

Converter

Drive

Motor

Multi-function
digital inputs
(default setting)

+V

A1

A2

A3

AC

(Reserved)

(Reserved)

(Reserved)

Control Circuit

-V

Analog Input 1

Analog Input 2

Analog Input 3

DIP Switch S1

Termination resistor
(120

Ω, 1/2 W)

DIP
Switch S2

R+

R-

S+

S-

IG

Three-
Phase
Power
Supply

Input-side AC

<1><2>

reactor

Harmonic filter module

<2>

U

V

W

X

Y

Z

R/L1

S/L2

T/L3

GFCI
or
MCCB

X

Y

Z

R/L1

S/L2

T/L3

r

t

CN5-A

CN5-B

CN5-C

Option card
connectors

Ground

Sink

Power supply
+10.5 Vdc, max. 20 mA

Power supply, -10.5 Vdc,
max. 20 mA

<5>

<3>

<3>

MA

MB

MC

Fault relay output
250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)

Multi-function relay output
(During MC on)
250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)

Multi-function relay output
(Operation Ready)
250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)

Multi-function relay
output (During Run 1)

<4>

250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)

M1

M2

M3

M4

M5

M6

0 V

FM

AM

AC

E (G)

<7>

<7>

Multi-function analog
output 1
(Output frequency)
-10 to +10 Vdc (2 mA) or
4 to 20 mA

Multi-function analog
output 2
(Output current)
-10 to +10 Vdc (2 mA) or
4 to 20 mA

FM

AM

SC

+24 V

Sink / Source mode
selection wire link
(default: Sink)

SP

SN

<6>

shielded line

twisted-pair shielded line

main circuit terminal

control circuit terminal

+

-

-

YAI

TOEP_C710656_07C_2_0.book 49 ページ 2015年1月9日 金曜日 午後6時23分

Advertising