Monitor data – Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 220

Advertising
background image

C.9 MEMOBUS/Modbus Data Table

220

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

Monitor Data

Monitor data can be read only.

Register No.

Contents

0020H

Converter Status 1
bit 0

During Run

bit 1

Reserved

bit 2

Operation Ready

bit 3

Fault

bit 4

Data Setting Error

bit 5

Multi-Function Relay Output (terminal M1-M2)

bit 6

Multi-Function Relay Output 1 (terminal M3-M4)

bit 7

Multi-Function Relay Output 2 (terminal M5-M6)

bit 8 - bit F

Reserved

0021H

Fault Contents 1
bit 0

Overcurrent (oC), Ground fault (GF)

bit 1

Overvoltage (ov)

bit 2

Converter Overload (oL2)

bit 3

Overheat 1 (oH1), Overheat 2 (oH2)

bit 4 - bit 6

Reserved

bit 7

EF to EF8: External Fault

bit 8

CPF: Hardware Fault (includes oF)

bit 9 - bit A

Reserved

bit B

Main Circuit Undervoltage (Uv)

bit C

Undervoltage (Uv1), Control Power Supply Undervoltage (Uv2), Soft Charge Circuit Fault
(Uv3)

bit D

Output Phase Loss (LF), Input Phase Loss (PF)

bit E

MEMOBUS/Modbus Communication Error (CE), Option Communication Error (bUS)

bit F

Operator Connection Fault (oPr)

0022H

Data Link Status
bit 0

Writing data or switching motors

bit 1 - bit 2

Reserved

bit 3

Upper or lower limit error

bit 4

Data conformity error

bit 5

Writing to EEPROM

bit 6 - bit F

Reserved

0023H - 0028H

Reserved

0029H

Fault Contents 2
bit 0

Reserved

bit 1

Ground Fault (GF)

bit 2 - bit F

Reserved

TOEP_C710656_07C_2_0.book 220 ページ 2015年1月9日 金曜日 午後6時23分