5.5 Operator Programming Errors

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

129

Tr

ou

blesh

oot

ing

5

Digital Operator

Display

Error Name

Detail

oPE04

Terminal Board
Mismatch Error

The converter or the removable terminal block with parameter backup was replaced.

Cause

Possible Solutions

The converter was replaced (but the removable
terminal block with parameter backup was not
replaced).

Set A1-03 to 5550 to load the parameter settings stored in the terminal board to the converter.
Initialize parameters after converter replacement by setting A1-03 to 2220.

The removable terminal block with parameter
backup was replaced.

Digital Operator

Display

Error Name

Detail

oPE05

Run Command
Selection Error

The settings for the Run Command or Bus Voltage Command are not correct.

Cause

Possible Solutions

The Run command is assigned to an option card
(b1-18 = 3) and an input option card is not
connected to the converter.

Reconnect the input option card to the converter.

The Run command is assigned to an option card
(b1-02 = 3) and an input option card is not
connected to the converter.

Digital Operator

Display

Error Name

Detail

oPE07

Multi-Function Analog

Input Selection Error A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10, or H3-06.

Cause

Possible Solutions

At least two of these parameters have the same
setting: H3-02, H3-10, or H3-06.

Change the settings to H3-02, H3-10, and H3-06 so that functions no longer conflict.
Note: Both 1F (Through mode) and F (Through mode) can be set to H3-02, H3-10, or H3-06
simultaneously.

Digital Operator

Display

Error Name

Detail

oPE30

Incorrect Input Voltage

Adjustment

The input voltage offset adjustment has not been performed.

Cause

Possible Solutions

• The setting of o2-04 (Drive Model Selection)

changed.

• ERPROM failed for the input voltage offset.

For information on clearing the fault, consult with your Yaskawa representative or the nearest
Yaskawa sales office.

TOEP_C710656_07C_2_0.book 129 ページ 2015年1月9日 金曜日 午後6時23分