H: multi-function terminals – Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 186

Advertising
background image

B.2 Parameter Tables

186

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

H: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.

No.

(Address

Hex)

Name

LCD Display

Description

Values

H1: Multi-Function Digital Inputs

H1-01

(438H)

Multi-Function
Digital Input
Terminal S1
Function Selection

Term S1 Func Sel

Assigns a function to the multi-function digital inputs S1
to S8.
Note: Set unused terminals to F.

Default: 4B
Min.: 1
Max.: 67

H1-02

(439H)

Multi-Function
Digital Input
Terminal S2
Function Selection

Term S2 Func Sel

Default: 4C
Min.: 1
Max.: 67

H1-03

(400H)

Multi-Function
Digital Input
Terminal S3
Function Selection

Term S3 Func Sel

Default: 24H
Min.: 0
Max.: 67

H1-04

(401H)

Multi-Function
Digital Input
Terminal S4
Function Selection

Term S4 Func Sel

Default: 14H
Min.: 0
Max.: 67

H1-05

(402H)

Multi-Function
Digital Input
Terminal S5
Function Selection

Term S5 Func Sel

Default: F
Min.: 0
Max.: 67

H1-06

(403H)

Multi-Function
Digital Input
Terminal S6
Function Selection

Term S6 Func Sel

Default: F
Min.: 0
Max.: 67

H1-07

(404H)

Multi-Function
Digital Input
Terminal S7
Function Selection

Term S7 Func Sel

Default: F
Min.: 0
Max.: 67

H1-08

(405H)

Multi-Function
Digital Input
Terminal S8
Function Selection

Term S8 Func Sel

Default: 8H
Min.: 0
Max.: 67

H1 Multi-Function Digital Input Selections

H1-

Setting

Function

LCD Display

Description

1

LOCAL/REMOTE selection

Local/Remote Sel

Open: REMOTE (parameter settings determine the source of the frequency
Reference 1 or 2 (b1-01, b1-02 or b1-15, b1-16)
Closed: LOCAL, Frequency reference and Run command are input from
the digital operator

8

Baseblock command (N.O.)

Ext BaseBlk N.O.

Closed: No converter output

9

Baseblock command (N.C.)

Ext BaseBlk N.C.

Open: No converter output

C

Analog terminal input selection Term A2 Enable

Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.

F

Through mode

Term Not Used

Select this setting when using the terminal in a pass-through mode.

14

Fault reset

Fault Reset

Closed: Resets faults if the cause is cleared and the Run command is
removed.

18

Timer function input

Timer function

Triggers the timer set up by parameters b4-01 and b4-02. Must be set in
conjunction with the timer function output (H2- = 12).

TOEP_C710656_07C_2_0.book 186 ページ 2015年1月9日 金曜日 午後6時23分