2.2 Mechanical Installation

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

29

Mec

h

an

ic

al

In

st

al

la

tio

n

2

2.2 Mechanical Installation

This section outlines specifications, procedures, and the environment for proper mechanical installation of the converter
and the harmonic filter module.

Installation Environment

Install the converter in an environment matching the specifications in

Table 2.1

to help prolong the optimum performance

life of the converter.

Table 2.1 Installation Environment

NOTICE: Avoid placing converter peripheral devices, transformers, or other electronics near the converter as the noise created can

lead to erroneous operation. If such devices must be used in close proximity to the converter, take proper steps to shield the converter

from noise.

NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the converter during installation. Failure to

comply could result in damage to the converter. Place a temporary cover over the top of the converter during installation. Remove the

temporary cover before converter start-up, as the cover will reduce ventilation and cause the converter to overheat.

NOTICE: When installing an IP00/IP20 converter in a closed panel or cabinet, sufficiently cool the panel or cabinet with a cooling fan or

air conditioner so that the air temperature entering the converter is 50

°C (122 °F) or cooler. Failure to comply could result in

overheating and fire.

Environment

Conditions

Installation Area

Indoors

Ambient

Temperature

IP00/Open Type enclosure: -10

°C to +50°C (14°F to 122°F)

IP20/Open Type enclosure: -10

°C to +40°C (14°F to 104°F)

Converter reliability improves in environments without wide temperature fluctuations.
When using the converter in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the converter or the harmonic filter module.

Humidity

95% RH or less and free of condensation

Storage

Temperature

-20

°C to +60°C (-4°F to +140°F)

Surrounding Area

Install the converter and the harmonic filter module in an area free from:

• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.

Altitude

1000 m (3281 ft) or lower, up to 3000 m (9843 ft) with derating. Refer to

Derating Data on page 178

for details.

Vibration

10 to 20 Hz at 9.8 m/s

2

, 20 to 55 Hz at 5.9 m/s

2

(2A0005 to 2A0050, 4A0005 to 4A0100)

10 to 20 Hz at 9.8 m/s

2

, 20 to 55 Hz at 2.0 m/s

2

(2A0065 to 2A0130, 4A0130 to 4A0370)

10 to 20 Hz at 5.9 m/s

2

, 20 to 55 Hz at 2.0 m/s

2

(4A0630)

Orientation

Install the converter vertically to maintain maximum cooling effects.