C.9 MEMOBUS/Modbus Data Table

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

221

MEMO

BUS/Mod

bus

Co

mmunica

tion

s

C

002AH

Alarm Contents 1
bit 0 - bit 2

Reserved

bit 3

Drive Baseblock (bb)

bit 4

Reserved

bit 5

Heatsink Overheat (oH)

bit 6

Overvoltage (ov)

bit 7

Undervoltage (Uv)

bit 8

Cooling Fan Error (Fan)

bit 9

MEMOBUS/Modbus Communication Error (CE)

bit A

Option Communication Error (bUS)

bit B - bit E

Reserved

bit F

Serial Communication Transmission Error (CALL)

002BH

Input Terminal Status
bit 0

Terminal S1 Closed

bit 1

Terminal S2 Closed

bit 2

Terminal S3 Closed

bit 3

Terminal S4 Closed

bit 4

Terminal S5 Closed

bit 5

Terminal S6 Closed

bit 6

Terminal S7 Closed

bit 7

Terminal S8 Closed

bit 8 - bit F

Reserved

002CH

Drive Status 2
bit 0

During Run

bit 1 - bit 5

Reserved

bit 6

Drive Ready

bit 7

During Undervoltage

bit 8

During Baseblock

bit 9

Voltage Reference from Operator Keypad

bit A

Run Command from Operator Keypad

bit B - bit C

Reserved

bit D

During Fault Restart

bit E

Fault

bit F

Communication Timeout

002DH

Output Terminal Status
bit 0

Multi-Function Relay Output 1 (terminal M1-M2)

bit 1

Multi-Function Relay Output 1 (terminal M3-M4)

bit 2

Multi-Function Relay Output 2 (terminal M5-M6)

bit 3 - bit 6

Reserved

bit 7

Fault Contact Output (terminal MA/MB-MC)

bit 8 - bit F

Reserved

Register No.

Contents