A.2 Converter Specifications

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

175

S

p

ec

ifi

ca

tio

n

s

A

A.2 Converter Specifications

Item

Specification

Input

Rated Voltage

Rated Frequency

200 V Class: 200 to 240 Vac 50/60 Hz
400 V Class: 380 to 480 Vac 50/60 Hz

Allowable Voltage

Fluctuation

-15 to +10%

Allowable Frequency

Fluctuation

±2%

Control

Characteristics

Control Method

Sine-wave PWM control

Input Power Factor

Input power factor of 0.99 minimum (for rated operation)

Output Voltage Accuracy

±5%

Overload Protection

Converter stops after 60 s at 150% of rated output current or after 3 s at 200% of rated output
current.

Voltage Reference Range

200 V Class: 300 to 360 Vdc
400 V Class: 600 to 730 Vdc

Carrier Frequency

Depends on the converter capacity

• 6 kHz 2A0005 to 2A0030, 4A0005 to 4A0060
• 4 kHz 2A0050 to 2A0130, 4A0100 to 4A0185
• 2 kHz 4A0270 to 4A0630

Main Control Functions

Torque Limit, Cooling fan on/off switch, Removable Terminal Block with Parameter
Backup Function, MEMOBUS/Modbus Communication (RS-422/RS-485 max, 115.2 kbps)

Protection

Functions

Momentary Overcurrent

Protection

Operation stops when input current exceeds 200%.

Open Fuse

Operation stops if the fuse opens.

Overload

Operation stops after 60 s at 150% of rated output current.
Operation stops after 3 s at 200% of rated output current.
(power supply and regeneration)

Overvoltage Protection

(Output)

200 V class: Stops when DC bus voltage exceeds approximately 410 Vdc
400 V class: Stops when DC bus voltage exceeds approximately 820 Vdc

Overvoltage Protection

(Input)

200 V class: Stops when input voltage exceeds approximately 227 Vac
400 V class: Stops when input voltage exceeds approximately 554 Vac

Undervoltage Protection

(Output)

200 V class: Stops when DC bus voltage is approximately 190 Vdc
400 V class: Stops when DC bus voltage is approximately 380 Vdc

Undervoltage Protection

(Input)

200 V class: Stops when input voltage is approximately 150 Vac
400 V class: Stops when input voltage is approximately 300 Vac

Momentary Power Loss

Ride-Thru

Immediate stop after Momentary Power Loss is detected.

Power Supply Frequency

Fault

Operation stops if the input frequency deviates by

±6 Hz of rated frequency.

Heatsink Overheat

Protection

Thermistor protection

Ground Protection

Electronic circuit protection

<1>

DC Bus Charge LED

Remains lit until DC bus voltage is 50 V

Environment

Area of Use

Indoors

Ambient Temperature

IP00/Open Type enclosure: -10

°C to +50°C (14°F to 122°F)

IP20/Open Type enclosure: -10

°C to +40°C (14°F to 104°F)

Humidity

95 RH% or less (no condensation)

Vibration/Shock

10 to 20 Hz at 9.8 m/s

2

, 20 to 55 Hz at 5.9 m/s

2

(2A0005 to 2A0050, 4A0005 to 4A0100)

10 to 20 Hz at 9.8 m/s

2

20 to 55 Hz at 2.0 m/s

2

(2A0065 to 2A0130, 4A0130 to 4A0370)

10 to 20 Hz at 5.9 m/s

2

, 20 to 55 Hz at 2.0 m/s

2

(4A0630)

Storage Temperature

-20

°C to +60°C (-4°F to +140°F)

Altitude

1000 m (3281 ft) or lower, up to 3000 m (9843 ft) with derating.

Protection Design

IP00/Open Type enclosure, IP20/Open Type enclosure