Backing up parameter values: o2-03, Parameter access level: a1-01 – Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 99

Advertising
background image

4.6 Verifying Parameter Settings and Backing Up Changes

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

99

S

ta

rt

-Up Pr

ogr

amming

&

O

p

er

at

io

n

4

4.6 Verifying Parameter Settings and Backing Up Changes

Use the Verify Mode to check all changes to parameter settings. Refer to

Verifying Parameter Changes: Verify Mode on

page 92

.

Save the verified parameter settings. Change the access level or set a password to the converter to prevent accidental
modification of parameter settings.

Backing Up Parameter Values: o2-03

Setting o2-03 to 1 saves all parameter settings to the converter internal memory. The converter can now recall all the
saved parameters by performing a User Initialization (A1-03 = 1110).

Parameter Access Level: A1-01

Setting the Access Level for “Operation only” (A1-01 = 0) allows the user to access parameters A1- and U-
only.

Other parameters are not displayed.

Setting the Access Level for “User Parameters” (A1-01 = 1) allows the user to access only the parameters that have been
previously saved as User Parameters. This is helpful when displaying only the relevant parameters for a specific
application.

No.

Parameter Name

Description

Setting

Range

Default

Setting

o2-03

User Defaults

Lets the user create a set of default settings for a User
Initialization.
0: Saved/Not Set
1: Set Defaults - Saves current parameter settings as the default
values for a User Initialization.
2: Clear All - Clears the currently saved user settings. After
saving the user parameter set value, the items of 1110 (User
Initialization) are displayed in A1-03 (User Parameter Default
Value).

0 to 2

0

A1-03

Initialize Parameters

Selects a method to initialize the parameters.
0: No Initialize
1110: User Initialization (The user must first program and store
desired settings using parameter o2-03)
2220: 2-Wire Initialization (parameter initialized prior to
shipment)
5550: oPE4 Fault reset

0, 0110, 2220,

5550

0

No.

Parameter Name

Description

Setting

Range

Default

Setting

A1-01

Access Level Selection

Selects which parameters are accessible via the digital operator.
0: Operation only. A1-01, A1-04, and A1-06 can be set and
monitored, and U- parameters can also be viewed.
1: User Parameters. Only recently changed parameters from
application parameters A2-01 to A2-16 and A2-17 to A2 -32 can
be set and monitored.
2: Advanced Access Level. All parameters can be set and
monitored.

0 to 2

2

TOEP_C710656_07C_2_0.book 99 ページ 2015年1月9日 金曜日 午後6時23分

Advertising