3.11 Wiring Checklist

NOTICE: Check all the wiring to ensure that all connections are correct after installing the converter and connecting any other devices.

Failure to comply could result in damage to the converter. To get the full performance life out of the electrolytic capacitors and circuit

relays, refrain from switching the converter power supply off and on more than once every 30 minutes.

No.

Item

Page

Converter, Peripherals, Option Cards

1

Check converter model number to ensure receipt of correct model.

23

2

Make sure you have the correct peripheral devices.

3

Check the option card model number.

Installation Area and Physical Setup

4

Ensure that the area surrounding the converter complies with specifications.

29

Power Supply Voltage, Output Voltage

5

The voltage from the power supply should be within the input voltage specification range of the
converter.

6

The total load must be within the output specifications of the converter.

24

7

A power supply with a capacity (kVA) that is larger than the rated input capacity of the converter must
be used.

8

The ratings must be correct.

24

Main Circuit Wiring

9

Confirm proper branch circuit protection as specified by national and local codes.

10

Properly wire the converter.

54

11

Suitable wires must be used to wire the power supply and converter.

62

12

Properly ground the converter. Review page

66

.

66

13

Tighten control circuit and grounding terminal screws.
Refer to

Wire Gauges and Tightening Torque on page 62

62

Control Circuit Wiring

14

Use twisted-pair line for all converter control circuit wiring.

79

15

Ground the shields of shielded wiring to the GND terminal.

49

16

Properly wire any option cards.

17

Check for any other wiring mistakes. Only use a multimeter to check wiring.

18

Properly fasten converter control circuit terminal screws. Refer to

Wire Size and Torque Specifications

on page 78

.

78

19

Pick up all wire clippings.

20

Ensure that no frayed wires on the terminal block are touching other terminals or connections.

21

Properly separate control circuit wiring and main circuit wiring.

22

The line between the input-side AC reactor and converter must be 10 m or shorter and the DC bus line
between the converter and drive must be 5 m or shorter.