2.3 Harmonic Filter Module Installation

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

39

Mec

h

an

ic

al

In

st

al

la

tio

n

2

2.3 Harmonic Filter Module Installation

Installation Environment

Install the harmonic filter module in an environment matching the specifications in

Table 2.8

to help prolong the optimum

performance life of the harmonic filter module.

Table 2.8 Installation Environment

WARNING! Fire Hazard. When installing an IP00/IP20 converter in a closed panel or cabinet, sufficiently cool the panel or cabinet with

a cooling fan or air conditioner so that the air temperature entering the converter is 50

°C (122 °F) or cooler. Failure to comply could

result in overheating and fire.

NOTICE: Avoid placing converter peripheral devices, transformers, or other electronics near the converter as the noise created can

lead to erroneous operation. If such devices must be used in close proximity to the converter, take proper steps to shield the converter

from noise.

NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the converter and harmonic filter module

during installation. Failure to comply could result in damage to the converter and the harmonic filter module. Place a temporary cover

over the top of the converter and the harmonic filter module during installation. Remove the temporary cover before converter and

harmonic filter module start-up, as the cover will reduce ventilation and cause the converter and the harmonic filter module to overheat.

Environment

Conditions

Installation Area

Indoors
Install the converter in an environment that does not easily accessible such as control panel.

Ambient

Temperature

IP00/Open Type enclosure: -10

°C to +50°C (14°F to 140°F)

Harmonic filter module reliability improves in environments without wide temperature fluctuations.
When using the harmonic filter module in an enclosure panel, install a cooling fan or air conditioner in the area to ensure
that the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the harmonic filter module.

Humidity

95% RH or less and free of condensation

Storage

Temperature

-20

°C to +60°C (-4°F to +140°F)

Surrounding Area

Install the harmonic filter module in an area free from:

• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.

Altitude

3000 m (9843 ft) or lower

Vibration

2.0 m/s

2

(20 to 55 Hz)