4.5 Operation with the Drive Connected

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

95

S

ta

rt

-Up Pr

ogr

amming

&

O

p

er

at

io

n

4

4.5 Operation with the Drive Connected

NOTICE: When installing a noise filter on the converter power supply, use a reactor-type noise filter (without a capacitor), such as a

zero phase reactor, and install it after the MCCB on the power supply side. Do not install a filter with a built-in capacitor as the harmonic

components may cause the capacitor to overheat or may damage the capacitor.

NOTICE: When installing a breaker or contactor on the converter side for an emergency shutoff, confirm that the CHARGE indicators

on the drive and converter are not lit before closing the breaker or contactor on the converter output (DC) side. If the power supply is

turned on while there is a voltage charge, an overcurrent will flow and the device may be damaged. Always confirm that the breaker or

contactor on the converter output (DC) side is turned on before applying power to the converter.

A1000 Connection Example

Figure 4.3

Figure 4.4 Standard Connection Diagram with A1000 (Example for CIMR-D2A0030, 2A0130, and 4A0030 to 4A0185)

<1> Do not use a line longer than 10 m (32.8 ft) to connect the input-side AC reactor and the converter.

<2> Use the specified AC reactor and harmonic filter module. Non-specified devices may cause erroneous operation.

<3> Do not use a DC bus line that is longer than 5 m (16.4 ft) to connect the converter and drive.

<4> Sequence the operation so that the converter starts operation before the drive when power is applied. Sequence the stopping

operation to turn off the drive first, then the motor, and finally the converter. Operating the drive without operating the converter or

turning off the power supply unit during operation may trigger a converter fault.

<5> Do not connect a power supply to the drive AC power supply terminals (R/L1, S/L2, and T/L3).

<6> The connections are shown for sequence connections with no-voltage contacts or NPN transistors for the sequence input signals

(S1 to S8). Use jumper S3 to select between Sink mode and Source mode. The default setting is Sink mode.

<7> For information on an interlock with the drive, refer to

Interlock with the Drive on page 97

.

D1000

+

-

E(G)

MA

MB

MC

(Reserved)

(Reserved)

(Reserved)

Shield ground terminal

Converter

Fault relay output
250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)

+V

A1

A2

A3

AC

R+

R-

S+

S-

IG

V

I

MEMOBUS/
Modbus Communication
RS-422/RS-485
max. 115.2 kbps

Control Circuit

-V

Power supply
+10.5 Vdc, max. 20 mA

Power supply, -10.5 Vdc,
max. 20 mA

Analog Input 1

Analog Input 2

Analog Input 3

DIP Switch S1

Multi-function relay output
(During MC on)
250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)

Multi-function relay output
(Operation Ready)
250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)

Multi-function relay
output (During Run 1)

<4>

250 Vac, max. 1 A
30 Vdc, max. 1 A
(min. 5 Vdc, 10 mA)

R/L1

S/L2

T/L3

CN5-A

CN5-B

CN5-C

Option card
connectors

S1 Forward Run / Stop

S2 Reverse Run / Stop

S3 External fault

S4 Fault reset

S5

S6

S7

S8

SC

Sequence common

Multi-function
digital inputs

Shield ground terminal

E(G)

A1000

Drive

+

R/L1

1

S/L2

T/L3

-

IM

U/T1

V/T2

W/T3

Ground

Motor

r1/ 11

1/ 21

t1/ 31

Ground

Three-
Phase
Power
Supply

Input-side AC

Harmonic Filter Module

U

V

W

X

Y

Z

GFCI
or
MCCB

X

Y

Z

R/L1

S/L2

T/L3

r

t

<1><2>

<2>

<3>

<5>

<7>

<3>

Termination resistor
(120 Ω, 1/2 W)
DIP Switch S2

M1

M2

M3

M4

M5

M6

S1

S2

S3

S4

S5

S6

S7

S8

SC

<6>

+24 V

RUN-SB

STOP

External fault

Fault reset

(Reserved)

(Reserved)

External Baseblock

(Reserved)

Multi-function

digital inputs

(default setting)

Sink / Source mode
selection wire link
(default: Sink)

SP

SN

0 V

FM

AM

AC

E (G)

Multi-function analog
output 1
(Output frequency)
-10 to +10 Vdc (2 mA) or
4 to 20 mA

Multi-function analog
output 2
(Output current)
-10 to +10 Vdc (2 mA) or
4 to 20 mA

FM

AM

shielded line

twisted-pair shielded line

main circuit terminal

control circuit terminal

-

+

-

YAI

TOEP_C710656_07C_2_0.book 95 ページ 2015年1月9日 金曜日 午後6時23分