YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

C.4 MEMOBUS/Modbus Setup Parameters

C.4 MEMOBUS/Modbus Setup Parameters

MEMOBUS/Modbus Serial Communication

This section describes parameters necessary to set up MEMOBUS/Modbus communications.

H5-01: Drive Slave Address

Sets the converter slave address used for communications.

Note: Cycle the power after changing this parameter to enable the new setting.

Each slave converter must be assigned a unique slave address for serial communications to work. Setting H5-01 to any
value besides 0 assigns the converter its address in the network. Slave addresses do not need to be assigned in sequential
order, but no two converters may share the same address.

H5-02: Communication Speed Selection

Sets the MEMOBUS/Modbus communications speed.

Note: Cycle the power after changing this parameter to enable the new setting.

Setting 0: 1200 bps
Setting 1: 2400 bps
Setting 2: 4800 bps
Setting 3: 9600 bps
Setting 4: 19200 bps
Setting 5: 38400 bps
Setting 6: 57600 bps
Setting 7: 76800 bps
Setting 8: 115200 bps

H5-03: Communication Parity Selection

Sets the parity used for communications.

Note: Cycle the power after changing this parameter to enable the new setting.

Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity

No.

Name

Setting Range

Default

H5-01

<1> If the address is set to 0, no response will be provided during communications.

Drive Slave Address

0 to FFH

<1>

1FH

No.

Name

Setting Range

Default

H5-02

Communication Speed Selection

0 to 5

3

No.

Name

Setting Range

Default

H5-03

Communication Parity Selection

0 to 2

0