5 operator programming errors, Operator programming errors – Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 128

Advertising
background image

128

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

5.5 Operator Programming Errors

5.5 Operator Programming Errors

Operator Programming Error Codes, Causes, and Possible Solutions

An Operator Programming Error (oPE) occurs when a contradictory parameter is set or an individual parameter is set to
an inappropriate value.

The converter will not operate until the parameter or parameters causing the problem are set correctly. An oPE, however,
does not trigger an alarm or fault output. If an oPE occurs, investigate the cause and refer to

Table 5.8

for the appropriate

action. When an oPE appears on the operator display, press the ENTER button to view U1-18 and see which parameter is
causing the oPE.

Table 5.8 oPE Codes, Causes, and Possible Solutions

Digital Operator

Display

Error Name

Detail

Err

EEPROM Write Error A verification mismatch occurred when writing data to the EEPROM.

Cause

Possible Solutions

The data was corrupted by noise when writing
data to the EEPROM.

• Press .
• Set the parameters again.
• Cycle the power supply. Refer to

Diagnosing and Resetting Faults on page 131

for details.

EEPROM Hardware Failure

Replace the board or converter. For information on board replacement, consult with your
Yaskawa representative or the nearest Yaskawa sales office.

Digital Operator

Display

Error Name

Detail

oPE01

Converter Capacity

Setting Fault

Converter capacity and the value set to o2-04 do not match.

Cause

Possible Solutions

The drive model selection (o2-04) and the
actual capacity of the converter are not the
same.

Correct the value set to o2-04.

Digital Operator

Display

Error Name

Detail

oPE02

Parameter Range

Setting Error

Use U1-18 to find parameters set outside the range.

Cause

Possible Solutions

Parameters were set outside the possible setting
range.

Set parameters to the proper values.

Note: When multiple errors occur simultaneously, other errors are given precedence over oPE02.

Digital Operator

Display

Error Name

Detail

oPE03

Multi-Function Input

Selection Error

A contradictory setting is assigned to multi-function contact inputs H1-01 to H1-08.

Cause

Possible Solutions

The same function is assigned to two
multi-function inputs. Excludes “Not used” and
“External Fault.”

• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.

TOEP_C710656_07C_2_0.book 128 ページ 2015年1月9日 金曜日 午後6時23分