5.4 Alarm Detection

126

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

Digital Operator

Display

Minor Fault Name

Detail

Alarm

Output

(H2-=10)

PF3

Input Phase Loss

Detection

Abnormal oscillation continued in the input power supply voltage. (Detected
when L8-69 = 1.)

YES

Cause

Possible Solutions

The fluctuation in the voltage of the input
power supply is too large.

Investigate the cause and implement countermeasures.
Refer to

Diagnosing and Resetting Faults on page 131

for details.

A phase loss occurred in the input power
supply.
The interphase voltage balance is bad.

Digital Operator

Display

Minor Fault Name

Detail

Alarm

Output

(H2-=10)

SE

MEMOBUS/Modbus

Test Mode Fault

A MEMOBUS/Modbus communications test was performed during operation.

YES

Cause

Possible Solutions

A fault occurred during MEMOBUS/Modbus
Communications Test Mode.

Always stop the operation of the converter before you perform MEMOBUS/Modbus
communications tests.

Digital Operator

Display

Minor Fault Name

Detail

Alarm

Output

(H2-=10)

SrC

Phase Order Fault

The phase order detection direction for the input power supply changed after the
power supply was turned on.

YES

Cause

Possible Solutions

A momentary power loss occurred.

Investigate and correct the cause and reset the fault.
Refer to

Diagnosing and Resetting Faults on page 131

for details.

An input power supply wiring terminal is loose.
The fluctuation in the voltage of the input
power supply is too large.

Digital Operator

Display

Minor Fault Name

Detail

Alarm

Output

(H2-=10)

Uv

Undervoltage

One of the following conditions was true when the converter was stopped and a
Run command was entered:

• DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the converter was opened.
• Low voltage in the control converter input power. This alarm outputs only if

L2-01 is not 0 and DC bus voltage is under L2-05.

YES

Cause

Possible Solutions

Phase loss in the converter input power.

Check for wiring errors in the main circuit input power. Correct the wiring.

Loose wiring in the converter input power
terminals.

• Ensure the terminals have been properly tightened.
• Apply the tightening torque to the terminals as specified. Refer to

Wire Gauges and Tightening

Torque on page 62

.

There is a problem with the converter input
power voltage.

• Check the voltage.
• Lower the voltage of the converter input power so that it is within the limits listed in the

specifications.

A power loss occurred.

Improve the power supply.

Internal circuitry is worn.

• Check the maintenance time for the capacitors (U4-05).
• Replace either the control board or the entire converter if U4-05 exceeds 90%. For instructions

on replacing the control board, contact Yaskawa or your nearest sales representative.

The converter input power transformer is too
small and voltage drops when the power is
switched on.

• Check for an alarm when the magnetic contactor, line breaker, and leakage breaker are closed.
• Check the capacity of the converter input power transformer.

Air inside the converter is too hot.

Check the temperature inside the converter.

The CHARGE light is broken or disconnected.

Replace either the control board or the entire converter. For instructions on replacing the control

board, contact Yaskawa or your nearest sales representative.