Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 187

Advertising
background image

B.2 Parameter Tables

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

187

Par

ame

te

r Li

st

B

1B

Program lockout

Program Lockout

Open: Parameters cannot be edited (except for U1-01 if the reference
source is assigned to the digital operator).
Closed: Parameters can be edited and saved.

24 to 27

2C to 2F

External fault

External fault
24: NO/ Always Det,
Coast to Stop
25: NC/Always Det,
Coast to Stop
26: NO/During RUN,
Coast to Stop
27: NC/During RUN,
Coast to Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only

24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)

47

Node Setup

Node SetUp

Closed: Node setup for SI-S3 enabled.

4B

Run Command
(2-wire Sequence)

Run Command3

Closed: Run
Note: To start operation, close the Stop Command (4C) and then open the
Run Command signal. After operation has started, it will continue even if
the Run Command signal is opened.

4C

Stop Command
(2-wire Sequence)

Stop Command3

Open: Stop.
Note: To stop operation, open the Stop Command signal.

67

Communications test mode

Comm Test Mode

Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays
“PASS” if the test completes successfully.

No.

(Address

Hex)

Name

LCD Display

Description

Values

H2: Multi-Function Relay Outputs

H2-01

(40BH)

Terminal M1-M2
function selection
(relay)

M1-M2 Func Sel

Refer to

H2 Multi-Function Relay Output Settings on

page 187

for a description of setting values.

Note: Set unused terminals to F.

Default: 25H
Min.: 0
Max.: 160

H2-02

(40CH)

Terminal M3-M4
Function Selection
(Relay)

P1/PC Func Sel

Default: 26H
Min.: 0
Max.: 160

H2-03

(40DH)

Terminal M5-M6
Function Selection
(Relay)

P2/PC Func Sel

Default: 6H
Min.: 0
Max.: 160

H2-06

(437H)

kWh Monitor Pulse
Output Unit Selection

Pwr Mon Unit Sel
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units

Select the output unit of the multi-function contact when
H2-01 to H2-03 is set to 39 and 3A.

1: 1 kWh Units
2: 10 kWh Units
3: 100 kWh Units
4: 1000 kWh Units

Default: 1
Min.: 1
Max.: 4

H2 Multi-Function Relay Output Settings

H2-

Setting

Function

LCD Display

Description

0

During run

During RUN 1

Closed: A Run command is active or voltage is output.

H1 Multi-Function Digital Input Selections

H1-

Setting

Function

LCD Display

Description

TOEP_C710656_07C_2_0.book 187 ページ 2015年1月9日 金曜日 午後6時23分

Advertising