C: tuning – Yaskawa D1000 Series Power Regenerative Converter User Manual

Page 183

Advertising
background image

B.2 Parameter Tables

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

183

Par

ame

te

r Li

st

B

C: Tuning

Tuning parameters set the voltage increase time, voltage decrease time, carrier frequency, and DC bus voltage control.

No.

(Address

Hex)

Name

LCD Display

Description

Values

C1: Voltage Increase and Decrease Times

C1-20

(265H)

Voltage Increase
Time

Vref Inc Ramp t

Sets the output voltage increase time in seconds.
Set the time to increase from 0% to 100%.
400 V Class: 800 V/C1-20 (V/s)
200 V Class: 400 V/C1-20 (V/s)

Default: 10.0 s
Min.: 0.0 s
Max.: 100.0 s

C1-21

(266H)

Voltage Decrease
Time

Vref Dec Ramp t

Sets the output voltage decrease time in seconds.
Set the time to decrease from 100% to 0%.
400 V Class: 800 V/C1-21 (V/s)
200 V Class: 400 V/C1-21 (V/s)

Default: 10.0 s
Min.: 0.0 s
Max.: 100.0 s

C6: Carrier Frequency

C6-03

(225H)

Carrier Frequency
Upper Limit

CarrierFreq Max

C6-03 is displayed on the operator, but cannot be set.

C7: DC Bus Voltage Control

C7-01

(253H)

DC Bus Voltage
Control (Avr)
Proportional Gain

AVR P Gain

Sets the proportional gain for DC bus voltage control
(Avr).

Default: 20.00
Min.: 1.00
Max.: 300.00

C7-02

(254H)

DC Bus Voltage
Control (Avr)
Integral Time

AVR I Time

Sets the integral time for DC bus voltage control (Avr).

Default: 0.500 s
Min.: 0.000 s
Max.: 10.000 s

C7-03

(255H)

DC Bus Voltage
Control (Avr)
Primary Delay Time
Constant

AVR Delay Time

Sets the primary delay time constant for DC bus voltage
control (Avr).

Default: 0.000 s
Min.: 0.000 s
Max.: 0.500 s

C7-12

(26EH)

Reactive Current
Reference Bias
Automatic
Calculation
Selection

React I Bias Sel

There is normally no need to change this parameter from
the default value. Sets whether to automatically calculate
the leading current compensation for the control process to
compensate the leading current in the reactive current
reference so that the leading current becomes 0.
0: Disabled
1: Enable (Automatically calculate the reactive current
reference bias.)

Default: 1
Range: 0, 1

C7-41

(1128H)

Gain for Active
Damping 2

Damp Gain 2

There is normally no need to change this parameter from
the default value.

Default: 0.000
Min.: 0.000
Max.: 10.000

C7-42

(1129H)

Gain for Automatic
Compensation of
Leading Current

Id Bias Gain

There is normally no need to change this parameter from
the default value.
It is used to make fine adjustments to the power factor.

Default: 100.0%
Min.: 0.0%
Max.: 1000.0%

C7-43

(112AH)

Input Voltage Offset
Adjustment

Vac Bias Adj Sel

There is normally no need to change this parameter from
the default value. This parameter is for factory setting.
If the setting is not correct, the converter may be damaged.
0: Standard
1: Start offset adjustment. (The parameter returns to 0 after
it is set.)
2: Offset adjustment not required. (The parameter returns
to 0 after it is set.)

Default: 0
Range: 0 to 2

C7-44

(112BH)

Gain for Active
Damping 3

Damping Gain 3

There is normally no need to change this parameter from
the default value.

Default: 0.00
Min.: 0.00
Max.: 1.00