2.2 Mechanical Installation
30
YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual
◆ Installation Orientation and Spacing
Install the converter upright as illustrated in
to maintain proper cooling.
Figure 2.1
Figure 2.1 Correct Installation Orientation
■
Single Converter Installation
shows the installation distance required to maintain sufficient space for airflow and wiring. Install the heatsink
against a closed surface to avoid diverting cooling air around the heatsink.
Figure 2.2
Figure 2.2 Correct Installation Spacing (Single)
A – 50 mm minimum
C – 120 mm minimum
B – 30 mm minimum
D – Airflow direction
A
C
A
B
B
C
Side Clearance
Top/Bottom Clearance
D
D