3.8 Harmonic Filter Module Wiring

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

69

El

ec

tr

ical

I

n

st

al

lat

ion

3

Terminal Functions

Table 3.5 Terminal Functions

Protecting Circuit Terminals

Insulation Caps or Sleeves

Use insulation caps or sleeves when wiring the module with crimp terminals. Take particular care to ensure that the wiring
does not touch nearby terminals or the surrounding case.

Wire Gauges and Tightening Torque

Use the tables in this section to select the appropriate wires and crimp terminals.

Note: 1. Wire gauge recommendations based on continuous current ratings using 75

°C 600 Vac vinyl-sheathed wire assuming ambient

temperature within 40

°C.

2. Wire gauge recommendations for models 4A0270 to 4A0630 based on continuous current ratings using 105

°C 600 Vac vinyl-sheathed

wire assuming ambient temperature within 40

°C.

Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge when the voltage drop is
greater than 2% of motor rated voltage. Ensure the wire gauge is suitable for the terminal block. Use the following
formula to calculate the amount of voltage drop:
Line drop voltage (V) =

× wire resistance (Ω/km) × wire length (m) × current (A) × 10

-3

Terminal

Type

Function

Page

R/L1

Main circuit power supply inputs

These terminals are connected to the power supply.

48

S/L2
T/L3

r

Power supply voltage detection inputs

These terminals are to detect the power supply voltage order
and voltage levels.

48

t

X

Harmonic filter module outputs

These terminals connect to the input-side AC reactor.

Y

Z

For 200 V class: 100

Ω or less

For 400 V class: 10

Ω or less

Grounding terminal

66

л3

TOEP_C710656_07C_2_0.book 69 ページ 2015年1月9日 金曜日 午後6時23分