3.10 Control I/O Connections

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

81

El

ec

tr

ical

I

n

st

al

lat

ion

3

3.10 Control I/O Connections

Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external
power supply for the digital inputs S1 to S8 as shown in

Table 3.13

(Default: Sink mode, internal power supply).

Note: Never short terminals SP and SN as doing so will damage the converter.

Table 3.13 Digital Input Sink / Source / External Power Supply Selection

Terminal A2 Input Signal Selection

Terminal A2 can be used to input either a voltage or a current signal. Select the signal type using switch S1 as explained
in

Table 3.14

. Set parameter H3-09 accordingly as shown in

Table 3.15

. Refer to

Figure 3.39

for locating switch S1.

To set the DIP switch, use tweezers or a tool with a tip width of approximately 0.8 mm.

Figure 3.42

Figure 3.39 DIP Switch S1

Table 3.14 DIP Switch S1 Settings

Converter Internal Power Supply

(Terminal SN and SP)

External 24 Vdc Power Supply

Sinking Mode (NPN)

Sourcing Mode (PNP)

Setting

Description

V (left position)

Voltage input (-10 to +10 V or 0 to 10 V)

I (right position)

Current input (4 to 20 mA or 0 to 20 mA): default setting

SC

S8

S7

24 Vdc

SP

SN

YAI

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc

YAI

SC

S8

S7

24 Vdc

SP

SN

YAI

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc

YAI

DIP switch S1

V

I