i.2 General Safety

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

13

Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.

Fire Hazard

Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the converter matches the voltage of the incoming power supply before applying power.

Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.

Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Do not install the converter to a combustible surface. Never place combustible materials on the converter.

Crush Hazard

Only allow qualified personnel to operate a crane or hoist to transport the converter.
Failure to comply may result in serious injury or death from falling equipment.

CAUTION

Do not carry the converter by the front cover or the terminal cover.
Failure to comply may result in minor or moderate injury from the main body of the converter falling.

NOTICE

Do not disconnect the wiring to the converter and harmonic filter module while the converter is outputting a
voltage.
Improper equipment sequencing could result in damage to the converter.

Connect a power supply with a capacity (kVA) that is larger than the rated input capacity (kW) of the converter.
Connecting a power supply with a capacity smaller than the rated input capacity may trigger an operating fault. If it is
necessary to connect a power supply with a capacity smaller than the rated input capacity, consult your Yaskawa
representative or the nearest Yaskawa sales office. Failure to comply may result in damage to the converter.

Observe proper electrostatic discharge procedures (ESD) when handling the converter, circuit boards, and
CMOSIC.
Failure to comply may result in ESD damage to the converter circuitry.

Do not perform a withstand voltage test on any part of the converter.
Failure to comply could result in damage to the sensitive devices within the converter.

Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.

W ARNING

TOEP_C710656_07C_2_0.book 13 ページ 2015年1月9日 金曜日 午後6時23分