B.2 Parameter Tables

190

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

L: Protection Function

Protection function parameters set momentary power loss processing, fault retries, and hardware protection.

No.

(Address

Hex)

Name

LCD Display

Description

Values

H4: Analog Outputs

H4-01

(41DH)

Terminal FM
Monitor Selection

Term FM FuncSel

Selects the data to be output through terminal FM.
Set the desired monitor parameter to the digits available in
U-.
For example, enter “153” for U1-53.

Default: 157
Min.: 000
Max.: 408

H4-02

(41EH)

Terminal FM
Monitor Gain

Terminal FM Gain

Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.

Default: 100.0%
Min.: -999.9%
Max.: 999.9%

H4-03

(41FH)

Terminal FM
Monitor Bias

Terminal FM Bias

Sets the signal level at terminal FM that is equal to 0% of the
selected monitor value.

Default: 0.0%
Min.: -999.9%
Max.: 999.9%

H4-04

(420H)

Terminal AM
Monitor Selection

Terminal AM Sel

Selects the data to be output through terminal AM.
Set the desired monitor parameter to the digits available in
U-.
For example, enter “153” for U1-53.

Default: 155
Min.: 000
Max.: 408

H4-05

(421H)

Terminal AM
Monitor Gain

Terminal AM Gain

Sets the signal level at terminal AM that is equal to 100% of the
selected monitor value.

Default: 50.0%
Min.: -999.9%
Max.: 999.9%

H4-06

(422H)

Terminal AM
Monitor Bias

Terminal AM Bias

Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.

Default: 0.0%
Min.: -999.9%
Max.: 999.9%

H4-07

(423H)

Terminal FM Signal
Level Selection

Level Select1
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA

Sets the signal level at terminal FM.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA

Default: 0
Min.: 0
Max.: 1

H4-08

(424H)

Terminal AM Signal
Level Selection

AO Level Select2
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA

Sets the signal level at terminal AM.
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA

Default: 0
Min.: 0
Max.: 1

No.

(Address

Hex)

Name

LCD Display

Description

Values

L2: Momentary Power Loss Ride-Thru

L2-01

(485H)

Momentary Power
Loss Operation
Selection

PwrL Selection
0: Disabled
1: Enbl with Timer
2: Enbl whl CPU act

0: Disabled. Converter trips on Uv1 fault when power is
lost.
1: Recover within the time set in L2-02. Uv1 will be
detected if power loss is longer than L2-02.
2: Recover as long as CPU has power. Uv1 is not detected.
Note: Even if L2-01 is set to 1 or 2 , the converter may
detect a fault when momentary-power-loss occurs during
regeneration or during no load.

Default: 0
Min.: 0
Max.: 2

L2-02

(486H)

Momentary Power
Loss Ride-Thru
Time

PwrL Ridethru t

Sets the Power Loss Ride-Thru time. Enabled only when
L2-01 = 1 or 3.

Default:

<2>

Min.: 0.0 s
Max.: 25.5 s

TOEP_C710656_07C_2_0.book 190 ページ 2015年1月9日 金曜日 午後6時23分