C.5 Converter Operations by MEMOBUS/Modbus

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

213

MEMO

BUS/Mod

bus

Co

mmunica

tion

s

C

C.5 Converter Operations by MEMOBUS/Modbus

The converter operations that can be performed by MEMOBUS/Modbus communication depend on converter parameter
settings. This section explains the functions that can be used and related parameter settings.

Observing the Converter Operation

A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of parameter
settings (except for H5- parameters):

• observe converter status and converter control terminal status from a PLC.
• read and write parameters.
• set and reset faults.
• set multi-function inputs.

Note: Input settings from the input terminals (S1 to S8) and from MEMOBUS/Modbus communications are both linked by a logical OR

operation.

Controlling the Converter

Select an external reference and adjust the parameters in

Table C.2

accordingly to start and stop the converter or set the

voltage reference using MEMOBUS/Modbus communications.

Table C.2 Setting Parameters for Converter Control from MEMOBUS/Modbus

Refer to

Voltage Reference Source on page 182

and

b1-02 (181H) on page 182

for details.

Reference Source

Parameter

Name

Required Setting

External Reference 1

b1-02

Run Command Selection 1

2

b1-18

Voltage Reference Source

2