5.7 Diagnosing and Resetting Faults

YASKAWA ELECTRIC TOEP C710656 07C YASKAWA Power Regenerative Converter - D1000 Instruction Manual

131

Tr

ou

blesh

oot

ing

5

5.7 Diagnosing and Resetting Faults

When a fault occurs and the converter stops, follow the instructions below to remove whatever conditions triggered the
fault, then restart the converter.

Fault Reset Methods

When a fault occurs, the cause of the fault must be removed and the converter must be restarted. The table below lists the
different ways to restart the converter.

Note: If the Run command is present, the converter will disregard any attempts to reset the fault. Remove the Run command before

attempting to clear a fault situation.

After the Fault Occurs

Procedure

Fix the cause of the fault, restart the
converter, and reset the fault

Press

on the digital operator when the

error code is displayed.

Resetting via Fault Reset Digital
Input S4

Close then open the fault signal digital input via
terminal S4. S4 is set for “Fault Reset” as
default (H1-04 = 14).

Turn off the main power supply if the above methods do not reset the fault. Reapply
power after the digital operator display has turned off.

LO
RE

F2

F1

ESC

RUN

STOP

ENTER

RESET

ALARM

DIGITAL OPERATOR JVOP-180

RESET

- MODE -

oC

Overcurrent

DRV

RESET

YAI

S4

Converter

Fault Reset Switch

SN

YAI

ON

OFF