background image

4.4 Trial Operation

4-31

4

Op

er

at

io

n

4.4.5 Setting Encoder Output Pulse

Set the encoder output pulse using the following parameter.

Note: The maximum setting for the encoder output resolution is 4096. When the number of divisions on the linear scale is

more than 4096, the data shown in 4.4.3 Feedback Resolutions of Linear Scale is no longer applicable.

Set the encoder output resolution for encoder pulse output signals (PAO, /PAO, PBO, /PBO) from the SER-

VOPACK to the host controller.

Feedback pulses per linear scale pitch (Pn282) are divided inside the SERVOPACK by the value set in Pn281

before being output. Set according to the system specifications of the machine or host controller.

The setting range varies with the motor maximum speed (Pn385) and linear scale pitch (Pn282).

The upper limit value for Pn281 can be obtained by the following equation.

Upper limit value for Pn281 =

× 72

Note: When the scale pitch is 4

μm, the motor maximum speed is limited to 1 ms/s because of the maximum response fre-

quency of serial converter unit.
If the set value is out of the setting range or does not satisfy the setting conditions, the alarm "Encoder Output Pulse
Setting Error" (A.041) is output.
If the motor speed exceeds the upper limit value according to the set encoder output resolution, the alarm "Over-
speed of Encoder Output Pulse Rate" (A.511) is output.
The upper limit of encoder output resolution is limited by the frequency dividing specification of serial converter
unit.

Setting Example

When the linear scale pitch = 20

μm (Pn282 = 2000) and the motor maximum speed = 5 m/s (Pn385 = 50),

Pn281 = 28 is accepted, but Pn281 = 29 is not accepted and A.041 is output.

Output Example

When Pn281 = 20 (20-edge output (5-pulse output) per linear scale pitch),

Note: When the linear scale is directly connected to the SERVOPACK and a serial converter unit is not used, Pn282 is not

valid. On the Un084 and Un085 monitors, check the linear scale pitch.

Pn281

Encoder Output Resolution

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

1 to 4096

1 edge/pitch

20

After restart

Setup

Speed

Position

Force

Pn282/100
Pn385

Phase A

Phase B

Linear scale pitch (Pn282)

Linear