3.7 Connecting Regenerative Resistors
3-35
3
Wirin
g and
Co
nnectio
n
(3) SERVOPACKs: Model SGDV-550A and -260D
No built-in regenerative resistor is provided, so the external regenerative resistor is required. The regenerative
resistor units are as follows:
Note: The regenerative resistor unit is constructed from a number of resistors.
Connect the B1/ and B2 terminals of the SERVOPACK to the R1 and R2 terminals of the regenerative resis-
tor unit.
When using a regenerative resistor unit, leave Pn600 at its factory setting. Set Pn600 when using a non-
YASKAWA external regenerative resistor.
Main Circuit
Power Supply
Applicable
SERVOPACK Model
SGDV-
Applicable
Regenerative
Resistor Unit
Resis-
tance (
Ω)
Specifications
Three-phase
200 V
550A
JUSP-RA05-E
3.13
Eight 25
Ω (220 W) resistors are connected
in parallel.
Three-phase
400 V
260D
JUSP-RA18-E
18
Two series of two 18
Ω (220 W) resistors
each are connected in parallel.
Regenerative Resistor Unit
JUSP-RA
-E
SERVOPACK