8.1 Alarm Displays

8-3

8

Trou

blesh

ooting

A.330

Main Circuit Power

Supply Wiring Error

• Setting of AC input/DC input is incorrect.
• Power supply wiring is incorrect.

Gr.1

Available

A.400

Overvoltage

Main circuit DC voltage is excessively high.

Gr.1

Available

A.410

Undervoltage

Main circuit DC voltage is excessively low.

Gr.2

Available

A.450

Main-Circuit

Capacitor Overvoltage

The capacitor of the main circuit has deteriorated or is
faulty.

Gr.1

N/A

A.510

Overspeed

The servomotor speed is above the maximum speed.

Gr.1

Available

A.511

Overspeed of Encoder

Output Pulse Rate

The motor speed upper limit of the set encoder output
resolution (Pn281) is exceeded.

Gr.1

Available

A.520

Vibration Alarm

Incorrect vibration at the motor speed was detected.

Gr.1

Available

A.521

Autotuning Alarm

Vibration was detected while performing tuning-less

function.

Gr.1

Available

A.550

Maximum Speed Setting

Error

The Pn385 setting is greater than the maximum speed.

Gr.1

Available

A.710

Overload: High Load

The servomotor was operating for several seconds to
several tens of seconds under a force largely exceeding
ratings.

Gr.2

Available

A.720

Overload: Low Load

The servomotor was operating continuously under a
force exceeding ratings.

Gr.1

Available

A.730
A.731

Dynamic Brake Overload

When the dynamic brake was applied, moving energy
exceeded the capacity of dynamic brake resistor.

Gr.1

Available

A.740

Overload of Surge

Current Limit Resistor

The main circuit power was frequently turned ON and

OFF.

Gr.1

Available

A.7A0

Heat Sink Overheated

The heat sink of the SERVOPACK exceeded 100

°C.

Gr.2

Available

A.7AB

Built-in Fan in SERVO-

PACK Stopped

The fan inside the SERVOPACK stopped.

Gr.1

Available

A.820

Encoder Checksum Error

The checksum results of linear scale memory is incor-
rect.

Gr.1

N/A

A.840

Encoder Data Error

Data in the linear scale is incorrect.

Gr.1

N/A

A.850

Encoder Overspeed

The linear scale was moving at high speed when the
power was turned ON.

Gr.1

N/A

A.860

Encoder Overheated

The internal temperature of linear scale is too high.

Gr.1

N/A

A.861

Motor Overheated

The internal temperature of motor is too high.

Gr.1

N/A

A.890

Encoder Scale Error

A linear scale fault occurred

Gr.1

N/A

A.891

Encoder Module Error

Linear scale is faulty.

Gr.1

N/A

A.A

*1

SERVOPACK: Command

Option Module Alarms

A.b31

Current Detection Error 1

The current detection circuit for phase U is faulty.

Gr.1

N/A

A.b32

Current Detection Error 2

The current detection circuit for phase V is faulty.

Gr.1

N/A

A.b33

Current Detection Error 3

The detection circuit for the current is faulty.

Gr.1

N/A

A.b6A

MECHATROLINK

Communications

ASIC Error 1

ASIC error occurred in the MECHATROLINK com-
munications.

Gr.1

N/A

A.b6b

MECHATROLINK

Communications

ASIC Error 2

ASIC error occurred in the MECHATROLINK com-
munications.

Gr.2

N/A

A.bF0

System Alarm 0

"Internal program error 0" of the SERVOPACK
occurred.

Gr.1

N/A

∗1. These alarms occur in SERVOPACKs with command option modules.

For details, refer to the manual for the command option module that is connected.

(cont’d)

Alarm

Number

Alarm Name

Meaning

Servo-

motor

Stopping

Method

Alarm

Reset