3.1 Main Circuit Wiring

3-9

3

Wirin

g and

Co

nnectio

n

(5) How to Select Molded-case Circuit Breaker and Fuse Capacities

The following table shows the SERVOPACK’s current capacities and inrush current.

Select a molded-case circuit breaker and fuses in accordance with these specifications.

Note 1. To comply with the EU low voltage directive, connect a fuse to the input side as protection against accidents

caused by short-circuits.
Select fuses or molded-case circuit breakers that are compliant with UL standards.
The table above also provides the net values of current capacity and inrush current. Select a fuse and a molded-
case circuit breaker which meet the breaking characteristics shown below.

• Main circuit, control circuit: No breaking at three times the current values shown in the table for 5 s.
• Inrush current: No breaking at the current values shown in the table for 20 ms.

2. The following restrictions apply to UL standard compliance conditions.

Main

Circuit

Power

Supply

Maximum

Applicable

Servomotor

Capacity

[kW]

SERVO-

PACK

Model

SGDV-

Power Sup-

ply Capacity

per SER-

VOPACK

[kVA]

Current Capacity

Inrush Current

Main Circuit

[Arms]

Control

Circuit

[Arms]

Main Circuit

[A0-p]

Control

Circuit

[A0-p]

Single-

phase,

100 V

0.05 R70F

0.2

1.5

0.38

16.5

35

0.1 R90F

0.3

2.5

0.2 2R1F

0.7

5

0.4 2R8F

1.4

10

Three-

phase,

200 V

0.05 R70A

0.2

1.0

0.2

33

70

0.1 R90A

0.3

1.0

0.2 1R6A

0.6

2.0

0.4 2R8A

1

3.0

0.5

3R8A

1.4

3.0

33

0.75 5R5A

1.6

6.0

1.0

7R6A

2.3

6.0

1.5

120A

3.2

7.3

0.25

2.0

180A

4

9.7

3.0

200A

5.9

15

5.0

330A

7.5

25

0.3

65.5

7.5

550A

14.6

37

Three-

phase,

400 V

0.5

1R9D

1.1

1.4

1.2

17

1.0

3R5D

2.3

2.9

1.5

5R4D

3.5

4.3

2.0

8R4D

4.5

5.8

1.4

34

3.0

120D

7.1

8.6

5.0

170D

11.7

14.5

57

7.5

260D

14.4

21.7

1.5

34

SERVOPACK Model SGDV-

Restrictions

180A, 200A

Available rated current for modeled-case circuit breaker: 40 A or less

330A

• Available rated current for non-time delay fuse: 70 A or less
• Available rated current for time delay fuse: 40 A or less
• Do not use single wires.

550A

• Available rated current for molded-case circuit breaker: 60 A or less
• Available rated current for non-time delay fuse or time delay fuse: 60 A or

less

260D

• Available rated current for molded-case circuit breaker: 60 A or less.
• Available rated current for non-time-delay fuse: 60 A or less.
• Available rated current for time delay fuse: 35 A or less