5 test without motor function, 1 motor information, 2 motor position and speed responses – Yaskawa Sigma-5 User Manual: Design and Maintenance - Linear Motors MECHATROLINK-III Communications Reference User Manual

Page 120: 1) when motor is connected, 2) when motor is not connected

Advertising
background image

4 Operation

4.5.1 Motor Information

4-32

4.5 Test Without Motor Function

The test without a motor is used to check the operation of the host controller and peripheral devices by simu-

lating the operation of the servomotor in the SERVOPACK, i.e., without actually operating a servomotor. This

function enables you to check wiring, verify the system while debugging, and verify parameters, thus shorten-
ing the time required for setup work and preventing damage to the machine that may result from possible mal-

functions. The operation of the motor can be checked during performing this function regardless of whether

the motor is actually connected or not.

Use Pn00C.0 to enable or disable the test without a motor.

4.5.1 Motor Information

The motor information that is used for a test without a motor is given below.

(1) When Motor is Connected

If a motor is connected, the information from the connected motor and the linear scale is used for the motor

and linear scale information. The set value of Pn00C.2 is not used.

(2) When Motor is Not Connected

The information for the virtual motor and the linear scale that is stored in the SERVOPACK is used. The set

value of Pn00C.2 is used for the linear scale information.

• Resolution: 256
• Scale pitch: The set value of Pn282

Encoder Type

The encoder information for the motor is set in Pn00C.2. A linear scale is always regarded as an incremental
linear scale.

4.5.2 Motor Position and Speed Responses

For the test without a motor, the following responses are simulated for references from the host controller

according to the gain settings for position or speed control.

• Servomotor position
• Servomotor speed
• Linear scale position

The load model, however, will be a rigid system with the mass ratio that is set in Pn103.

Parameter

Meaning

When

Enabled

Classification

Pn00C

n.

0

[Factory setting]

Disables the test without a motor.

After restart

Setup

n.

1

Enables the test without a motor.

Reference

Reference

Response

Response

Host controller

SERVOPACK

Simulates the operation
without motor.

65

Parameter

Meaning

When

Enabled

Classification

Pn00C

n. 0
[Factory setting]

Sets an incremental linear scale as an encoder type for
the test without a motor.

After restart

Setup

n. 1

Sets an absolute linear scale as an encoder type for the
test without a motor.