8.4 Troubleshooting Malfunction Based on Operation and Conditions of the Servomotor

8-35

8

Trou

blesh

ooting

Absolute Linear

Scale Position

Difference Error

(The position

saved in the host

controller when

the power was

turned OFF is

different from the

position when the

power was next

turned ON.)

Noise interference due to incorrect
cable specifications of linear scale
connection cables.

The linear scale connection cables
must be tinned annealed copper
shielded twisted-pair or screened
unshielded twisted-pair cable with a
core of 0.12 mm

2

min.

Use the specified linear scale con-
nection cables.

Noise interference due to length of

linear scale connection cables.

Check the length of the linear scale

connection cables.

The length of each cable must be

equal to or shorter than the maxi-
mum wiring length listed here.

• Connection cables for serial con-

verter unit: 20 m

• Connection cables for linear

scale: 15 m

• Connection cables for hall sensor:

15 m

Noise interference due to damaged

linear scale connection cables.

Check if the linear scale connection
cables are bent and the sheaths are
damaged.

Replace the linear scale connection

cables and correct the cable layout.

Excessive noise to the linear scale
connection cables.

Check if the linear scale connection
cables are bundled with a high-cur-
rent line or near a high-current line.

Correct the cable layout so that no
surge is applied.

FG potential varies because of

influence of machines such as weld-

ers at the servomotor.

Check if the machines are correctly

grounded.

Ground machines correctly, and

prevent diversion to the FG on the

linear scale side.

SERVOPACK pulse counting error

due to noise interference

Check if there is noise interference

on the I/O signal line from the serial

converter unit.

Take measures against noise in the

serial converter unit wiring.

Excessive vibration and shock to

the linear scale

Check if vibration from the machine

occurred or linear scale installation

is incorrect (mounting surface accu-

racy and fixing method).

Reduce vibration from the machine,

or secure the linear scale installa-

tion.

A linear scale fault occurred.

Replace the linear scale.

A SERVOPACK fault occurred.
(The pulse count does not change.)

Replace the SERVOPACK.

Host controller serial data reading

error

Check the error detection section of

the host controller.

Correct the error detection section

of the host controller.

Check if the host controller is exe-

cuting data parity checks.

Execute a serial data parity check.

Check noise in the cable between

the SERVOPACK and the host con-

troller.

Take measures against noise, and

again execute a serial data parity

check.

(cont’d)

Problem

Probable Cause

Investigative Actions

Corrective Actions