5 Adjustments

5.9.2 Mode Switch (P/PI Switching)

5-62

(2) Operating Examples for Different Switching Conditions

Using the Force Reference [Factory Setting]

With this setting, the speed loop is switched to P control when the value of force reference input exceeds the

force set in Pn10C. The factory setting for the force reference detection point is 200% of the rated force.

Using the Speed Reference

With this setting, the speed loop is switched to P control when the value of speed reference input exceeds the

speed set in Pn181.

Using Acceleration

With this setting, the speed loop is switched to P control when the speed reference exceeds the acceleration set

in Pn182.

Using the Position Error

With this setting, the speed loop is switched to P control when the position error exceeds the value set in
Pn10F.

This setting is effective with position control only.

Motor speed

Speed reference

Speed

+Pn10C

Force
Reference

- Pn10C

Force reference

PI Control

PI Control

0

PI

P

P

Time

Linear

Speed reference

Speed

Motor speed

Time

P Control

PI Control

Pn181

PI

Linear

Motor

speed

Speed reference

Speed

Motor acceleration

+Pn182

Acceleration

- Pn182

PI Control

PI Control

0

PI

P

P

Time

Linear

Position
error

Speed reference

Speed

Motor speed

Time

P Control

PI Control

Pn10F

PI