7 absolute linear scales, 1 absolute data request (sens on command) – Yaskawa Sigma-5 User Manual: Design and Maintenance - Linear Motors MECHATROLINK-III Communications Reference User Manual

Page 126

Advertising
background image

4 Operation

4.7.1 Absolute Data Request (SENS ON Command)

4-38

4.7 Absolute Linear Scales

If using an absolute linear scale, a system to detect the absolute position can be designed for use with the host

controller. As a result, an operation can be performed without a zero point return operation immediately after

the power is turned ON.

For details on how to set up the absolute linear scale, refer to 5 Trial Operation (Checking Linear Servomotor

Operation) in the

Σ

-V Series User’s Manual, Setup, Linear Motor (No.: SIEP S800000 44).

Set Pn002.2 to 0 (factory setting) to use the absolute linear scale.

4.7.1 Absolute Data Request (SENS ON Command)

The Turn Sensor ON command (SENS_ON) must be sent to obtain absolute data as an output from the SER-

VOPACK.

The SENS_ON command is sent at the following timing.

∗ Send the SENS_OFF command to turn OFF the control power supply.

Parameter

Meaning

When

Enabled

Classification

Pn002

n. 0

[Factory setting]

Uses the absolute linear scale as an absolute linear
scale.

After restart

Setup

n. 1

Uses the absolute linear scale as an incremental linear
scale.

SERVOPACK control
power supply

5 seconds max.

ON

OFF

OFF

ON (Normal status)

OFF

OFF

ON

50 ms

Serial data

(Phase A)

(Phase B)

(Phase B)

Approx.

15 ms

400 ms max.

1 to 3 ms

60 ms max.
(90 ms typ.)

The servomotor will not be turned ON even if the SV_ON command is received during this interval.

ALM signal OFF
(Alarm status)

SENS_ON
(Turn Sensor ON)

PAO

PBO

Servomotor power

Undefined

Undefined

(Phase A)

OFF

OFF

OFF

OFF

*

ON

Incremental

pulses

Incremental

pulses

Initial incremental

pulses

Initial incremental

pulses

65