3) setting monitor factor – Yaskawa Sigma-5 User Manual: Design and Maintenance - Linear Motors MECHATROLINK-III Communications Reference User Manual

Page 156

Advertising
background image

5 Adjustments

5.1.3 Monitoring Operation during Adjustment

5-6

The following signals can be monitored by selecting functions with parameters Pn006 and Pn007.
Pn006 is used for analog monitor 1 and Pn007 is used for analog monitor 2.

∗ Refer to 5.8.1 Switching Gain Settings for details.

(3) Setting Monitor Factor

The output voltages on analog monitors 1 and 2 are calculated by the following equations.

Parameter

Description

Monitor Signal

Unit

Remarks

Pn006
Pn007

n.

00

[Pn007

Factory

Setting]

Motor moving speed

1 V/1000 mm/s

n.

01

Speed reference

1 V/1000 mm/s

n.

02

[Pn006

Factory

Setting]

Force reference

1 V/100% rated force

n.

03

Position error

0.05 V/1 reference unit

0 V at speed/force control

n.

04

Position amplifier error

0.05 V/1 linear scale

pulse unit

Position error after electronic

gear conversion

n.

05

Position reference speed

1 V/1000 mm/s

n.

06

Reserved (Do not change.)

n.

07

Reserved (Do not change.)

n.

08

Positioning completed

Positioning completed:
5 V
Positioning not com-
pleted: 0 V

Completion indicated by out-
put voltage.

n.

09

Speed feedforward

1 V/1000 mm/s

n.

0A

Force feedforward

1 V/100% rated force

n.

0B

Active gain

*

1st gain: 1 V
2nd gain: 2 V

Gain type indicated by output
voltage.

n.

0C

Completion of position reference

Completed: 5 V
Not completed: 0 V

Completion indicated by out-
put voltage.

n.

0D

Reserved (Do not change.)

Analog monitor 1 output voltage = (-1)

×

Signal selection

(Pn006=n.00

غغ) (Pn552)

Analog monitor 2 output voltage = (-1)

×

Signal selection

(Pn007=n.00

غغ)

×

Multiplier + Offset voltage [V]

×

Multiplier + Offset voltage [V]

(Pn550)

(Pn551)

(Pn553)