8.1 Alarm Displays

8-23

8

Trou

blesh

ooting

A.F10:
Main Circuit Cable

Open Phase
(With the main power

supply ON, voltage was
low for more than 1 sec-
ond in an R, S, or T
phase.)
(Detected when the main
power supply was turned
ON.)

The three-phase power supply

wiring is incorrect.

Check the power supply wiring.

Confirm that the power supply is

correctly wired.

The three-phase power supply is

unbalanced.

Measure the voltage at each phase

of the three-phase power supply.

Balance the power supply by chang-

ing phases.

A single-phase power is input

without setting Pn00B.2 (power

supply method for three-phase

SERVOPACK) to 1 (single-phase

power supply).

Check the power supply and the

parameter setting.

Match the parameter setting to the

power supply.

A SERVOPACK fault occurred.

Turn the power supply OFF and

then ON again. If the alarm still

occurs, the SERVOPACK may be

faulty. Replace the SERVOPACK.

A.F50:
Servomotor Main

Circuit Cable

Disconnection
(The servomotor did not

operate or power was not

supplied to the servomo-

tor even though the

SV_ON (Servo ON)

command was input

when the servomotor

was ready to receive it.)

A SERVOPACK fault occurred.

The SERVOPACK may be faulty.

Replace the SERVOPACK.

The wiring is not correct or there

is a faulty contact in the motor

wiring.

Check the wiring.

Make sure that the servomotor is

correctly wired.

FL-1

*2

:

System Alarm

SERVOPACK failure

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.

FL-2

*2

:

System Alarm

CPF00:
Digital Operator

Transmission Error 1

The contact between the digital
operator and the SERVOPACK is
faulty.

Check the connector contact.

Insert securely the connector or
replace the cable.

Malfunction caused by noise
interference.

Keep the digital operator or the
cable away from noise sources.

CPF01:
Digital Operator
Transmission Error 2

A digital operator fault occurred.

Disconnect the digital operator and
then re-connect it. If the alarm still
occurs, the digital operator may be
faulty. Replace the digital operator.

A SERVOPACK fault occurred.

Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be

faulty. Replace the SERVOPACK.

∗2. These alarms are not stored in the alarm history and are displayed only in the panel display.

(cont’d)

Alarm Number:

Alarm Name

(Alarm Description)

Cause

Investigative Actions

Corrective Actions