1 mechatrolink-iii communications settings, 1 setting switches s1, s2, and s3, 1) settings of the rotary switches s1 and s2 – Yaskawa Sigma-5 User Manual: Design and Maintenance - Linear Motors MECHATROLINK-III Communications Reference User Manual

Page 91: 2) settings of the dip switch s3, M-iii

Advertising
background image

4.1 MECHATROLINK-III Communications Settings

4-3

4

Op

er

at

io

n

4.1 MECHATROLINK-III Communications Settings

This section describes the switch settings necessary for MECHATROLINK-III communications.

4.1.1 Setting Switches S1, S2, and S3

The DIP switch S3 is used to make the settings for MECHATROLINK-III communications.

The station address is set using the rotary switches S1 and S2.

(1) Settings of the Rotary Switches S1 and S2

Set the station address using the rotary switches S1 and S2.

(2) Settings of the DIP Switch S3

The following table shows the settings of the DIP switch (S3).

L1
L2

CN

4

3

5

2

6

1

7

C

8

0

F

9

E

A

D

B

S1

4

3

5

2

6

1

7

C

8

0

F

9

E

A

D

B

S2

ON

OFF

1234

S3

M-III

Station Address

S1

S2

00H to 02H: Disabled
(Do not use these addresses.)

0

0 to 2

03H (Factory setting)

0

3

04H

0

4



EFH

E

F

F0H to FFH: Disabled
(Do not use these addresses.)

F

0 to F

S3

Function

Setting

Factory

setting

Pins 1 and 2

Sets the number of

transmission bytes.

1

2

Number of transmission bytes

1: OFF

2: ON

OFF

OFF

16 byte

ON

OFF

32 byte

OFF

ON

48 byte

ON

ON

Reserved.
(Do not use this setting.)

Pin 3

Reserved. (Do not change.)

OFF

Pin 4

Reserved. (Do not change.)

OFF

• When using the MECHATROLINK-III standard servo profile, set the number of transmis-

sion bytes to either 32 or 48.

• When using the MECHATROLINK-II-compatible profile, set the number of transmission

bytes to either 16 or 32.

• Turn the power OFF and then ON again to enable the new settings.

Advertising