5.1 Type of Adjustments and Basic Adjustment Procedure

5-9

5

Adjustments

Related Parameter

Related Alarm

(4) Vibration Detection Function

Set the vibration detection function to an appropriate value with the vibration detection level initialization
(Fn01B). For details on how to set the vibration detection function, refer to 6.16 Vibration Detection Level

Initialization (Fn01B).

(5) Excessive Position Error Alarm Level at Servo ON

If position errors remain in the error counter when turning ON the servomotor power, the servomotor will

move and this movement will clear the counter of all position errors. Because the servomotor will move sud-

denly and unexpectedly, safety precautions are required. To prevent the servomotor from moving suddenly,
select the appropriate level for the excessive position error alarm level at servo ON (Pn526) to restrict opera-

tion of the servomotor.

Related Parameters

Related Alarms

When an alarm occurs, refer to 8 Troubleshooting and take the corrective actions.

Pn520

Excessive Position Error Alarm Level

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

1 to 1073741823

1 reference unit

5242880

Immediately

Setup

Alarm Dis-

play

Alarm Name

Meaning

A.d00

Position Error Overflow

Position errors exceeded parameter Pn520.

Position

Pn526

Excessive Position Error Alarm Level at Servo ON

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

1 to 1073741823

1 reference unit

5242880

Immediately

Setup

Position

Pn528

Excessive Position Error Warning Level at Servo ON

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

10 to 100

1%

100

Immediately

Setup

Pn584

Speed Limit Level at Servo ON

Classification

Setting Range

Setting Unit

Factory Setting

When Enabled

0 to 10000

1 mm/s

10000

Immediately

Setup

Position

Position

Alarm Dis-

play

Alarm Name

Meaning

A.d01

Position Error Overflow
Alarm at Servo ON

This alarm occurs if the servomotor power is turned ON when the position
error is greater than the set value of Pn526 while the servomotor power is
OFF.

A.d02

Position Error Overflow
Alarm by Speed Limit at
Servo ON

When the position errors remain in the error counter, Pn584 limits the speed
if the servomotor power is turned ON. If Pn584 limits the speed in such a
state, this alarm occurs when position references are input and the number of
position errors exceeds the value set for the excessive position error alarm

level (Pn520).