7

Applications

7.19

Fan

178

Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Required torque of the fan
From the data entered and the load characteristic selected the DSD calculates the required torque.

[7-174] Load characteristics of the fan

Calculation of the torque for a quadratic load characteristic (M ≈ n²):

[7-175] Equation 3: Torque for a quadratic load characteristic

Calculation of the torque for a constant load characteristic (M ≈ constant):

[7-176] Equation 4: Torque for a constant load characteristic

Tip!
Further equations to complete the calculations required for an application can be found in

the chapter "

Basic calculations

".

( 68)

• The host computer "Energy efficiency fan/pump" serves to compare the energy de-

mand in an inverter-controlled and mechanically controlled system.

 Constant characteristic (M ≈ constant)
 Square-law characteristic (M ≈ n²)
 Rated point of the fan

M

n

0

1

2

M

App

M

N

n

N

η

Vlt

---------

2

J

add

α

+

=

M

App

M

N

J

add

α )

(

+

=