18

Drive dimensioning messages

18.8

Inverters

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.8.7

Current resolution is not adapted to the motor

18.8.8

Utilisation of the inverter >100 %

18.8.9

Utilisation of the inverter too high after mains connection

Note!

The current resolution of the inverter is not adapted to the motor. The rated motor current is vvv A. Thus

the max. output current of the inverter of www A is much greater than the rated motor current.

The factor for the ratio of the rated motor current and the max. output current of the inverter is xxx.

The factor is still reasonable.

The factor zzz must not be exceeded.

Note!

The current resolution of the inverter is not adapted to the motor. The rated motor current is vvv A. Thus

the max. output current of the inverter of www A is much greater than the rated motor current.

The factor for the ratio of the rated motor current and the max. output current of the inverter is xxx.

The factor is still reasonable.

The factor zzz must not be exceeded.

Cause

Effects

Possible remedies

Due to the high rated current of the

inverter compared to the rated mo-

tor current, the current detection in

the inverter is unfavourable with re-

gard to the motor currents.

Unfavourable control properties and

a disadvantageous behaviour with

regard to smooth running.

• Select a smaller inverter.

• Select an inverter with an over-

load behaviour that is better

adapted.

Dimensioning criteria ( 346)

Warning!

The max. utilisation of the inverter is xxx %, regarding the power pulse current.

Thus the limit value of 100 % is exceeded.

Cause

Effects

Possible remedies

The inverter is overloaded by a too

high and too long current pulse (e.g.

due to an acceleration process).

The device is switched off with an er-

ror message due to device utilisation.

• Select a more powerful inverter.

• Change motion or load profile to

reduce the height or duration of

the current pulse.

Warning!

The I×t utilisation directly after mains connection and with max. ambient temperature is max. xxx %. The

drive cannot start with the motion profile.

Cause

Effects

Possible remedies

After mains connection, the inverter

is overloaded by a too high and too

long current pulse (e.g. due to an ac-

celeration process).

For safety reasons, a preload of the

inverter is assumed before mains

connection.

The device is switched off with an er-

ror message due to device utilisation.

• Switch on a load with a short de-

lay.

• Select a more powerful inverter.

• Change motion or load profile to

reduce the height or duration of

the current pulse.