18.11.4

Utilisation >100 %, regarding the peak braking power

18.11.5

Regenerative power is not dissipated safely

Warning!

The max. utilisation of the brake chopper is xxx %. Thus the limit value of 100 % is exceeded.

Cause

Effects

Possible remedies

The actual peak braking power per

brake chopper is too high.

An overvoltage message is activated

within the inverter.

• Use larger drive.

• Generate a DC-bus system and

use multiple brake choppers of

the devices in the DC-bus system

if required. Observe the respective

Hardware Manual!

Warning!

The dissipation of the regenerative power is not guaranteed.

Cause

Effects

Possible remedies

No electrical brake system has been

selected for the hoist drive.

The hoist drive cannot brake the load

safely. Even in DC-bus operation, sit-

uations can arise where the regener-

ative power is not absorbed by other

drives.

Select brake components if no other

braking method is available.