18

Drive dimensioning messages

18.8

Inverters

468

Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.8.10

Control mode VFCplus without feedback is not permissible

18.8.11

The SLVC control mode is not permissible for inverters >55 kW

18.8.12

Too low braking torques at low speed

18.8.13

Motor limit rating is exceeded

Warning!

For the hoist drive, the Servo Drive 9400 combination greater than 55 kW is not permissible with the VFC-

PLUS control type without feedback.

Cause

Effects

Possible remedies

The control mode is not suitable for

hoist drives.

The drive must not be operated in

this control mode.

Select a control mode with feedback.

Warning!

The SLVC control mode is not permissible for inverters with a rating of more than 55 kW.

Cause

Effects

Possible remedies

The SLVC control mode must not be

used for inverters in this power

range.

The drive must not be operated in

this control mode. The control is not

stable!

Select a control mode with feedback.

Note!

The drive system only develops small amounts of braking torque at low speeds in SLVC operating mode.

Use alternative braking methods such as DC-injection braking or mechanical brakes.

Cause

Effects

Possible remedies

The drive system only develops small

amounts of braking torque at low

speeds in the SLVC control mode.

At low speeds with operation in gen-

erator mode, the motor cannot be

controlled.

• Select a control mode with feed-

back.

• In this control mode, do not oper-

ate the drive permanently at low

speeds .

• Do not use the control mode with

hoist drives.

Warning!

The rated motor power is xxx kW. In the "V/f control" mode, the max. motor limit rating of yyy kW is ex-

ceeded. The selected drive system cannot ensure a safe hoist operation.

Cause

Effects

Possible remedies

The rated motor power is too high for

a hoist drive with V/f characteristic

control.

At low speeds, the motor is magnet-

ised as required. Overheating and

torque losses are the result. In this

control mode, a safe operation is not

possible.

Select a control mode with feedback.