Unearthed power systems
IT systems are power systems with an isolated neutral. They are used in the following countries and

industry sectors:

• In the public supply system in France and Belgium
• Chemical industry
• Mining
• Island power supplies (own generator)
• Hospitals
• Ship's mains
• Crane, conveyor, and hoist systems
• Paper and pulp industry

Advantages of the IT systems are the high fire and operator safety. Furthermore there is no discon-

nection during the first earth fault.

9.2

Ambient conditions

9.2.1

Max. ambient temperature, motor/gearbox

The permissible load capacity depends on the ambient temperature. The load capacity also depends

on whether a geared motor or a motor without a gearbox is used.

Tip!
If a geared motor is used, the derating starts from a temperature of 30 °C, in the case of a

motor without a gearbox it starts from 40 °C.

Depending on the site altitude, the following correction values k

ϑ

result for geared motors:

ϑ

opr

k

ϑ

1000 m

2000 m

3000 m

4000 m

20 °C

1.15

1.04

0.92

0.81

30 °C

1

0.9

0.8

0.70

40 °C

0.8

0.72

0.64

0.56

50 °C

0.6

0.54

0.48

0.42

60 °C

0.4

0.36

0.32

0.28