18

Drive dimensioning messages

18.2

Drive system

446

Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.2.4

Product has been discontinued

18.2.5

No effective starting current limitation available

18.2.6

Dissipation of the regenerative power is not guaranteed

18.2.7

Checking the drive system and the tensile force sensor

Tip!

The distribution for product xxx will cease soon.

Recommendation: Select an alternative product or contact your Lenze distribution partner.

Cause

Effects

Possible remedies

The product has been discontinued

and shall not be used anymore for

drive dimensioning.

Maybe the product is not available

anymore.

• Select current product.

• Contact Lenze sales partner.

Note!

No effective starting current limitation available.

For DC-bus capacity of the DC-bus connection, an external charging connection may be required.

Cause

Effects

Possible remedies

Without an effective starting current

limitation, the devices must not be

connected in parallel.

Devices will be destroyed.

Take appropriate measures after

consultation with your Lenze sales

partner.

Note!

During the dimensioning phase, no measures for the dissipation of generated power have been taken.

The hoist drive generates regenerative power during the lowering phase that has to be dissipated.

Cause

Effects

Possible remedies

A hoist drive generates regenerative

power during the lowering operation

that has to be dissipated by the in-

verter.

The lowering operation has not been

configured in the DSD.

Hoist sags.

• Use electrical braking compo-

nents.

• Use regenerative power supply

modules.

Note!

Check whether the drive system and the tensile force sensor are suitable for the torque setting range xxx

and the tensile force setting range yyy.

Recommendation: Use low-friction mechanical transmission elements between the motor and the wind-

ing shaft as well as a KTY sensor for the compensation of the motor temperature.

Cause

Effects

Possible remedies

The torque setting range results from

the entered values for tensile force

and diameter.

Minimum tensile forces cannot be

reached or cannot be repeated.

• Carry out recommended meas-

ures.