2 drive system, 1 utilisation >100 %, regarding the max. torque, 18 drive dimensioning messages – Lenze DSD User Manual

Page 445

Advertising
background image

Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23

445

18

Drive dimensioning messages

18.2

Drive system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.2

Drive system

18.2.1

Utilisation >100 %, regarding the max. torque

18.2.2

In the DC-bus connection, the braking circuit of the inverter is not checked

18.2.3

In the DC-bus connection, the EMC protection of the device is ineffective

Warning!

The utilisation of the motor-inverter combination relative to the required max. torque of the application

is xxx %. Thus the limit value of 100 % is exceeded.

Cause

Effects

Possible remedies

The max. torque required by the ap-

plication is higher than the torque

provided by the motor-inverter com-

bination.

The drive cannot activate the appli-

cation:

• The acceleration capacity does

not suffice.

• The speed that is required is not

achieved.

• In the case of hoist drives, the load

can drop.

Check the max. torque on the basis of

the motor characteristic.

M-n characteristic ( 316)

Note!

In the DSD, only one central braking circuit can be dimensioned.

In a DC-bus connection, the braking circuit of the inverter is ignored.

Cause

Effects

Possible remedies

In the DC-bus connection, the DSD

does not check the brake choppers in

the single drive axes.

• In the DSD, you can only dimen-

sion one central brake chopper for

the supply concept.

If the braking circuit of the single

drive axis is dimensioned incorrectly,

the brake chopper or brake resistor

will be destroyed.

Fire hazard!

• Only use the brake chopper when

the regenerative energy is dissi-

pated safely.

• Check the brake chopper of the

single drive axis manually.

• Use results calculated by DSD.

Note!

The EMC protection of the device is not effective in the DC-bus connection. Check whether EMC measures

are required for the entire DC-bus connection or machine.

Cause

Effects

Possible remedies

In the DC-bus operation, the EMC

protection integrated in the device is

not effective or only partially effec-

tive.

EMC Directives may possibly not ob-

served.

Take EMC measures for the entire

DC-bus connection or the entire ma-

chine.