4 motor is operated in the field weakening range, 6 motor speed too low, Max. mismatch is higher than permissible mismatch – Lenze DSD User Manual

Page 456: 18 drive dimensioning messages

Advertising
background image

18

Drive dimensioning messages

18.5

Lenze motor

456

Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.5.4

Motor is operated in the field weakening range

18.5.5

Max. mismatch is higher than permissible mismatch

18.5.6

Motor speed too low

Note!

The field weakening factor of the motor is xxx.

Hence, the limit value of yyy is exceeded. The motor is operated in the field weakening range.

During field weakening operation, larger reserves must be provided for the inverter.

Cause

Effects

Possible remedies

In the field weakening range, the ac-

curacy of the DSD current model is re-

stricted.

DSD cannot calculate correctly the

thermal utilisation of the inverter.

The inverter is thermally overloaded. Select inverter with higher thermal

reserves.

Field weakening ( 426)

Note!

The max. mismatch of the motor is xxx.

Hence, the max. permissible mismatch of the motor of yyy is exceeded.

(only applicable to speed-controlled systems)

Cause

Effects

Possible remedies

The maximum mismatch exceeds

the limit value defined.

The drive is inclined to vibrations and

possibly is not controllable with re-

gard to feedback control (only for

speed control or position-controlled

systems).

For torque-controlled or VFCPLUS-

controlled systems this value has a

lower priority.

• Select gearbox with higher trans-

mission ratio.

• Select motor with higher inertia

(standard motor instead of servo

motor).

Load-matching factor ( 321)

Tip!

The required max. motor speed is xxx rpm. Thus it falls below the limit value for low motor speeds of

yyy rpm.

Cause

Effects

Possible remedies

With regard to their size, inverters

are defined by the motor current. If

the motor is only operated in the

lower speed range with regard to its

rated speed, the voltage provided by

the inverter is not utilised.

A different motor that would be op-

erated more near its rated speed

would improve the utilisation of the

inverter.

Drive system possibly may not be at

optimal cost.

Use a gearbox with a higher ratio, so

that the motor at the same power is

better utilised with regard to speed,

and the inverter is better utilised

with regard to voltage.