Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23

479

18

Drive dimensioning messages

18.11

Brake chopper

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.11

Brake chopper

18.11.1

Ambient temperature of the brake chopper too high

18.11.2

Permissible site altitude of the brake chopper exceeded

18.11.3

Permanent utilisation of the brake chopper > 100 %

Warning!

The ambient temperature of the inverter is xxx °C. Thus the max. permissible ambient temperature of the

brake chopper of yyy °C is exceeded.

Cause

Effects

Possible remedies

The permissible ambient tempera-

ture is exceeded.

The drive gets too hot and switches

itself off (provided that a thermal

contact is available and is evaluated).

Fire hazard if the thermal contact is

not evaluated!

Contact Lenze.

Warning!

The site altitude is xxx m. It thus falls below the max. permissible site altitude of the brake chopper of

yyy m.

Cause

Effects

Possible remedies

Due to the lower atmospheric pres-

sure, the cooling effect of the air is re-

duced.

The drive gets too hot and switches

itself off (provided that a thermal

contact is available and is evaluated).

Fire hazard if the thermal contact is

not evaluated!

Contact Lenze.

Warning!

The permanent utilisation of the brake chopper is xxx %. Thus the limit value of 100 % is exceeded.

Cause

Effects

Possible remedies

The brake resistor is continuously

overloaded.

The brake resistor gets too hot.

• The thermal contact is opened.

Fire hazard if the thermal contact is

not evaluated!

Use larger drive.