4 max. thermal utilisation >100, 5 control mode not suitable for hoist drive, 6 inverter designed as double axis – Lenze DSD User Manual

Page 466: Max. thermal utilisation >100 % ( 466), 18 drive dimensioning messages

Advertising
background image

18

Drive dimensioning messages

18.8

Inverters

466

Lenze · Drive Solution Designer · Manual · DMS 4.2 EN · 12/2013 · TD23

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.8.4

Max. thermal utilisation >100 %

18.8.5

Control mode not suitable for hoist drive

18.8.6

Inverter designed as double axis

Warning!

The max. thermal utilisation of the inverter is xxx %. Thus the limit value of 100 % is exceeded.

Cause

Effects

Possible remedies

The inverter is operated at a too high

continuous current.

The inverter switches itself off via the

device monitoring (Ixt).

• Select a greater inverter.

• Improve the utilisation of the in-

verter voltage range:

• If the motor is not operated at

rated speed, it might be possi-

ble to improve the utilisation of

the voltage range by adapting

the gearbox ratio, and thus re-

duce the current required.

Note!

The selected control mode xxx is not suitable for safely operating the hoist.

Cause

Effects

Possible remedies

With the selected control mode, the

drive is not able to safely provide the

required torque over the entire con-

trol range continuously.

The hoist may crash.

Select other control modes.

Note!

The motor output of the inverter is a double axis.

The design in this DSD project only refers to one output of this double axis.

The second output can be dimensioned in a second DSD project.

Cause

Effects

Possible remedies

For double axes, DSD checks every

axis individually. It is not checked

whether both parts of the double

axis are also used in the DC-bus sys-

tem.

Not all parts of the double axis are

used or the double axis is used too of-

ten.

Check manually.