The inverters are designed for a temporary overcurrent. The utilisation by a defined, cyclic operation

is determined via the "Ixt" monitoring function. The I×t function consists of two moving averages

which are checked in parallel:

• A short-time moving average of the apparent motor current for a pulse utilisation.
• A continuous moving average of the apparent motor current for a continuous utilisation.

The characteristics of typical load functions and the simulation of the "Ixt" function are shown in the

following illustration:

[11-22] Overcurrent capability for Inverter Drives 8400 at 45 °C

Type of utilisation

Utilisation cycle

Condition for the monitoring func-

tion

Pulse utilisation

15 s

I

rated,out

> 160 %

Permanent utilisation

180 s

The monitoring function is switched

on continuously.

Pulse utilisation (cycle of 15 s)

 Peak current
 Limited current during the recovery time

Δt

1

Load with peak current (typically 3 s)

Δt

2

Recovery time with limited current (typically 12 s)

Permanent utilisation (cycle of 180 s)

 Peak current
 Limited current during the recovery time

Δt

3

Load with peak current (typically 60 s)

Δt

4

Recovery time with limited current (typically 120 s)

t

0

100

2

0

1

I

[%]

N,out

3

Dt

1



‚

Dt

2

Dt

3

Dt

4