Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 101

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

101

Logging

Chapter 6

Setpoint_Log_Mode

Setpoint_Log_Mode defines the log behavior when full.

0 = Stop logging
1 = Overwrite oldest record

Time_Of_Use_AutoStore

Time_Of_Use_AutoStore defines the day of the month to start a new time-of-
use log record.

Off_Peak_Days

Off_Peak_Days is a bit field that specifies off-peak days of the week.

Bit 0 = Sunday, bit 1 = Monday, and so forth

MID_Peak_AM_Hours
MID_Peak_PM_Hours
ON_Peak_AM_Hours
ON_Peak_PM_Hours

These parameters are bit fields specifying mid-peak and on-peak hours of the
weekdays not already defined as off-peak. Bit 0 = 12 a.m. …1 a.m.,
bit 1 = 1 a.m.…2 a.m. and so forth.

Load_Factor_Auto_Log_Setting

Load_Factor_Auto_Log_Setting defines the day of month to start a new load
factor log record.

PowerQuality_Log_Mode

This parameter sets the action of the log once it has filled to capacity.

0 = Stop logging
1 = Overwrite oldest record