Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 312
312
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
5
Int16
Input_I2_Mapping
This parameter logically maps a physical current channel to I2.
1 = I1
2 = I2
3 = I3
-1 = I1 inverted
-2 = I2 inverted
-3 = I3 inverted
2
-3…-1
1…3
6
Int16
Input_I3_Mapping
This parameter logically maps a physical current channel to I3.
1 = I1
2 = I2
3 = I3
-1 = I1 inverted
-2 = I2 inverted
-3 = I3 inverted
3
-3…-1
1…3
7
Int16
Last_Cmd_Rejection_Status
0 = No rejection
1 = Rejected see rejection status
0
0…1
8
Int16
Rejection_Information
0 = No information
1 = Selected range is incomplete
2 = Command is already active. Please use command 5 to start over.
3 = Two like inputs wired to one terminal
4 = Invalid Input parameter
0
0…4
9…13
Int16
Reserved
Future Use
0
0
Table 120 - Status.Wiring_Corrections Data Table
Element
Number
Type
Tag Name
Description
Default
Range