312

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

Appendix A

PowerMonitor 5000 Unit Data Tables

5

Int16

Input_I2_Mapping

This parameter logically maps a physical current channel to I2.
1 = I1
2 = I2
3 = I3
-1 = I1 inverted
-2 = I2 inverted
-3 = I3 inverted

2

-3…-1
1…3

6

Int16

Input_I3_Mapping

This parameter logically maps a physical current channel to I3.
1 = I1
2 = I2
3 = I3
-1 = I1 inverted
-2 = I2 inverted
-3 = I3 inverted

3

-3…-1
1…3

7

Int16

Last_Cmd_Rejection_Status

0 = No rejection
1 = Rejected see rejection status

0

0…1

8

Int16

Rejection_Information

0 = No information
1 = Selected range is incomplete
2 = Command is already active. Please use command 5 to start over.
3 = Two like inputs wired to one terminal
4 = Invalid Input parameter

0

0…4

9…13

Int16

Reserved

Future Use

0

0

Table 120 - Status.Wiring_Corrections Data Table

Element
Number

Type

Tag Name

Description

Default

Range