Technical specifications, Appendix b, Appendix – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 367

Advertising
background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

367

Appendix

B

Technical Specifications

Table 191 - Accuracy and Range

Parameter

Accuracy in % of Reading at 25 °C (77 °F) 50/60 Hz Unity Power Factor

Rating, nom/Metering Range, max

Applies to
1426-M5

Voltage Sense Inputs: V1, V2, V3, VN

±0.1%

X

Line-neutral RMS: 398V AC/15…660V AC
Line-line RMS: 690V AC /26…1144V AC

VG

X

Connect to power system earth ground
only. This is a functional ground.

Current Sense Input: I1, I2, I3, I4

±0.1%

X

5 A / 0.05 - 15.6 A RMS

Frequency

±0.05 Hz

X

50 or 60 Hz / 40…75 Hz

Power Functions: kW, kVA, kVAR
Demand Functions: kW, kVA, kVAR
Energy Functions: kWh, kVAh, kVARh

ANSI C12.20 -2010

Class 0.2

(1)

Clause 5.5.4

EN 62053-22 -2003

Class 0.2 Accuracy

(1)

Clause 8

X

Metering Update Rates

One update per line cycle;
1024 samples per cycle per channel

X

(1) For catalog number 1426-M5E (PN-54351) units manufactured from July 2012

January 2013, the accuracy is Class 0.5 not Class 0.2. All other characteristics and products are not impacted. The

impacted units are those with manufacturing date codes of 0712, 0812, 0912, 1012, 1112, 1212, 0113.

Table 192 - Input and Output Ratings

Parameter

Rating, nom

Range, max

Control Power (L1, L2)

120/240V AC 50/60 Hz (38VA)
Or
120/240V DC (26VA)

85…264V AC 47…63 Hz
Or
106…275V DC

Control Power (24V DC)

24V DC (12 VA)

22.8…25.2V DC